3. Installation
RuggedCom® RuggedSwitch® 19 RSG2300 Installation Guide Rev 110
3.2.3.2. DC Power Supply Wiring Examples RSG2300 and RSG2300P
+
Figure 3.17. DC Single Power Supply Wiring Example
+
+
Figure 3.18. DC Dual Redundant
Power Supply Wiring Example
RSG2300P will always have a 48VDC power supply in position PS2.
125/250VDC rated equipment: A 300VDC appropriately rated circuit breaker must
be installed.
A circuit breaker is not required for 12-24 or 48 VDC rated power supplies.
For dual DC power supplies, separate circuit breakers must be installed and
separately identified.
Equipment must be installed according to the applicable country wiring codes.
3.2.3.3. AC and DC Power Supply Wiring Example RSG2300 and RSG2300P
+
Figure 3.19. AC and DC Power Supply Wiring Example